Pipe fall calculator.Set the laser, not the guesswork.

Pick the pipe size and type the exact run length, grade and start depth. Get fall in millimetres, the ratio and your end invert depth, with minimum grades checked for every size. Copy it, text it or save the PDF. Free, no email.

Pipe size

DN100 (standard sewer drain), minimum grade 1.65% (1:60)

m
%

Ratio 1:60

mm

198mm fall

DN100 over 12m at 1.65% (1:60)

Start invert 500mm → end invert 698mm below datum.

At or above the DN100 minimum. That's 1.6mm of fall per metre, set your laser to it.

SizeMin gradeRatioFall over your 12m
DN402.5%1:40300mm minimum
DN502.5%1:40300mm minimum
DN652.5%1:40300mm minimum
DN801.65%1:60198mm minimum
DN901.65%1:60198mm minimum
DN1001.65%1:60198mm minimum
DN1501%1:100120mm minimum

Guide only, using the minimum grades commonly applied under AS/NZS 3500.2. Long runs, high fixture loads, pumped sections and council/authority requirements change the design. The licensed plumber and the approved plans win, not this page.

Your numbers stay on this device and come back next time. Nothing is uploaded.

The numbers every drainer carries in their head, on a page

DN100 at 1:60 is 16.5mm a metre. Everyone knows it until it's 4:30pm, the trench is open, the connection point is 480mm down and you're working out whether a 14 metre run still gets there above it. That's 231mm of fall, end invert 711mm, and now you know before the excavator does.

Slide the grade and watch the invert move. The table under the result shows the minimum fall for every common size over your run, so checking an alternative is one glance rather than another round of mental arithmetic in the rain.

Questions

What fall does a sewer pipe need in Australia?

The minimum grades commonly applied under AS/NZS 3500.2: DN100 drains at 1.65% (about 1:60), DN65 and smaller wastes at 2.5% (1:40), DN150 at 1% (1:100). That's 16.5mm of fall per metre of DN100. The calculator flags anything below minimum for the size you pick.

How do I work out the fall for my run?

Fall = length × grade. A 12 metre DN100 run at 1.65% needs 12 × 16.5 = 198mm of fall. Put your start invert depth in and the calculator gives the end invert too, which is the number you actually dig to.

Can a drain have too much fall?

The old 'water outruns the solids' rule is largely a myth at normal grades, steeper generally flushes better, and AS/NZS 3500.2 doesn't set a maximum grade for typical gravity drains. The real limits are practical: available depth at the connection point, and vertical drops needing the right fittings. What kills drains is too little fall, not too much.

Is this a substitute for the approved design?

No. Long runs, high fixture unit loads, boundary trap requirements, pumped sections and council or water authority conditions all change the design, and the approved plans win. This tool is for the on-site moment: you know the run and the size, you need the fall in millimetres before you set the laser.